Activity1: Item rates for the work "Replacement of OCB by VCB"
Do you want replace the existing Oil Circuit Breaker by the new Vacuum Circuit Breaker?
Worrying about the specifications of VCB?
Expecting some information regarding the item rates for the estimation ?
Here item rates are provided to help you.
Item 1: Dismantling
of the existing 11KV, 400 amps, 250MVA capacity "Reyrolle burn" make
Oil Circuit Breaker together with P.T. by dismantling incoming and outcoming
cables and shifting it to a suitable location in Electrical sub-station as per
the directions of engineer-in-charge.
Unit: Lump sum
Quantity: 1 Job
Unit rate (Rs): 10,000/-
Amount (Rs): 10,000/-
Item 2: Supply, installation, testing and
commissioning of 3 phase, 3 wire, 50Hz, 11KV, 400amps 13.1 KA (250MVA) breaking
capacity, indoor floor mounting type totally enclosed, fully interlocked, metal
clad VCB as perIEC-62271-100/200 with single break trip free breaker, motor/manual
operated closing spring charged mechanism, mounted on a truck carriage,
complete with self contained fully interlocked rack in & rack out
mechanism, hand trip devices, mechanical ON & OFF Push buttons with
indicators, spring release coil, shunt trip coil, auxiliary switch of 6 No.
& 6 NC, Panel Indication lamps for breaker ON/OFF/TRIP/TRIP circuit
healthy/ spring charge etc., accessories such as heater with heater switch
& thermostat, cubicle illumination lamp etc., side cable box with bushings and
cable glands suitable for 11 KV 3Cx95 Sq.mm XLPE cable; 2 core CTs for metering
with accuracy class 0.5 and protection with accuracy class P10, 15VA, 50/5+5A;
overload, short circuit & earth fault relays: metering panel consisting of
ammeter, volt meter, frequency & power factor meters: 11000/110 volts,
100VA, PT for metering, Schneider/ABB or equivalent make, all complete together
with the cost of material, labour, transport, tools & plants and as per the
specifications and directions of engineer-in-charge.
Unit: Each
Quantity: 1 No.
Unit rate (Rs): 4,47,000/-
Amount (Rs): 4,47,000/-
Item 3: Supply
of 11KV, 3 core, 95/70 sq.mm XLPE cable conforming to the relevant IS
specifications.
Unit: Meter
Quantity: 40.
Unit rate (Rs): 2,500/-
Amount (Rs): 1,00,000/-
Item 4: End
terminations of 11KV, 3 core, 95/70 Sq.mm XLPE / PVC cable along with the jointing
materials such as heavy duty crimping type lugs, cable compound/putty,
Empire/HT tapes etc., complete with the cost of jointing materials, labour
tools & implements & as per the directions of engineer-in-charge.
Unit: Each
Quantity: 4 set.
Unit rate (Rs): 15,000/-
Amount (Rs): 60,000/-
Item 5: Buy-back
offer for the existing 11KV, 400 Amps, 250 MVA capacity "Reyrolle
burn" make oil circuit breaker together with P.T., on where is as is
basis. The contractor has to lift the OCB at his own cost and risk and the
amount thus quoted for taking back the OCB will be deducted/adjusted against
the bill for other items.
Unit: Lump Sum
Quantity: 1 No.
Unit rate (Rs): 10,000/-
Amount (Rs): 10,000/-
Total
= Net ( 1 + 2 + 3 + 4 - 5)=Rs. 6,07,000/-
Note: The above shown rates may be varied as per the location. This is for providing general information only.